Compressor Application Manual
53
Figure 37 - Short relay without capacitor Figure 38 - Short relay with capacitor
Terminal 13
Terminal 11
Terminal 13
Terminal 11
Comments:
a) FG compressors for HST applications make
it obligatory to use the starting capacitor and
must be installed according to figure 38;
b) The FG compressor relay for HST
applications is different from that used in
FF compressors with regard to the following
aspects:
VIVI
terminals 11 and 13 are longer than normal
to permit capacitor's connection;
it does not have the copper wire bridge
between terminals 11 and 13.
The compressor, therefore, will only start if
the corresponding capacitor is installed. In
the start relay in figure 37, one power lead
must be connected to the thermal protector
(terminal 3) and the other to terminal 10 of
the relay;
c) the use of a different capacitor from those
recommended in the previous table may
affect the performance of the thermal
protector and cause the motor to burn out.
Terminal 10