Compressor Application Manual
17
4 - Thermostat
4.1 - Thermostat switched off
Turn the thermostat button to maximum
(coldest) and see if the compressor starts.
4.2 - Thermostat with no current passing
through contacts
Install a bridge wire between the
thermostat terminals. If the compressor
starts, substitute the thermostat.
4.3 - Thermostat does not switch off
Check if the thermostat bulb is correctly
installed. Turn the thermostat button to
the minimum (least cold) and check if the
compressor disconnects. If the problem
continues, substitute the thermostat.
4.4 - Thermostat adjusted to the
maximum (coldest)
Turn the thermostat button to the
minimum (least cold) and check if the
compressor disconnects within the range
of use. Regulate the thermostat and
instruct the user how to use it correctly.
4.5 - Thermostat adjusted to the
minimum (least cold)
Regulate the thermostat to the correct
position and instruct the user how to use
it correctly.