Compressor Application Manual
45
totally empty, switch on the
resistance of the charge cylinder to
increase the pressure and release
the refrigerant to the refrigeration
system. If it is not possible to
increase the pressure in the charge
cylinder through the resistance,
you may lock the register of the
charge cylinder, switch the
compressor on and then slowly
open it until the correct refrigerant
charge is transferred.
This operation requires that the
refrigeration professional takes
great care. In the case of
excessive refrigerant fluid, the
compressor may draw in the liquid
refrigerant fluid and break the
cylinder joints or other components.
Any fault will detract from the
system's good performance.
10.4 -10.4 -
10.4 -10.4 -
10.4 - Closing the sealed unit
a) With the compressor connected,
flatten the process tube as close
as possible to the fast coupling
(1). Next, again flatten it, keeping
the pliers fixed to the tube (2) and
switch the compressor off.
b) Break the tube at the first flattened
point and check to see if there is
any leakage. If not, solder the end
of the tube. Remove the pliersand
check to see if there is no leakage.
The system must be
accompanied for the first
hour after starting up!
!
Caution