Compressor Application Manual
44
V
10.2 -10.2 -
10.2 -10.2 -
10.2 -
If you are using scales and charge-
receiver cylinder:
a) Weigh the empty cylinder. The
correct charge will be the quantity
supplied by the manufacturer plus
the weight of the empty cylinder;
b) With the compressor switched off,
connect the receiving cylinder to
the process tube.
1) Open the valve of the receiving
cylinder and wait until the
pressure has equalized
(cylinder/sealed unit).
2) Close the receiving cylinder
valve and switch on the
compressor.
3) Gradually open the receiving
cylinder valve.
4) After removing the cylinder,
weigh it to make sure that it is
completely empty.
10.3 -10.3 -
10.3 -10.3 -
10.3 - If using a charging cylinder with
graduated band:
a) Write down the volume of the
column relating to the refrigerant
to be used.
b) Connect the cylinder to the
process tube. With the compressor
switched off, open the register until
the quantity stipulated by the
manufacturer flows out or until the
pressures in the refrigeration
system cylinder are equal. If it
equalizes before the charge is