Compressor Application Manual
40
V
To complete the cleaning operation, proceed as
follows:
• Place a fast coupling on the return line
and connect it on the cleaning machine's
outlet side;
• Connect the capillary to the
cleaning machine’s suction
side, leaving it operating
for around 15 minutes;
• Blast some nitrogen
into this circuit to
remove any cleaning
fluid residue.
Lastly, the condenser
must be cleaned. To do so,
you must repeat the previous
operation, connecting one end of the condenser to
the outlet side and the other to the cleaning
machine's suction tube.
5 - Installation of filter drier
• Make a small bend in the capillary to
prevent it from going too far into the filter,
approximately 15 mm (0.59”);
• Using a clamp, open up the two sides
of the filter drier when brazing;
Figure 27 - Capillary tube
Figure 28 - Inserting the capillary into
the filter drier
If it is not possible to use a blowtorch with
proper capacity to braze the oil cooler tubes
(TRO) in the system's tubes, proceed as follows:
before placing the compressor in the refrigeration
system, tip it to the opposite side from the TRO,
braze approximately 50 mm (1.97”) copper
tube at each end of the TRO. With the TRO
extended, it will certainly not be
difficult to braze it onto the
system's tubes.
Important
!
15 mm
(0.59”)
Only use filters that
contain molecular sieve
desiccants inside.
Important
!