Compressor Application Manual
42
V
At the other end of this tube, install a fast coupling or
similar register to make the vacuum and gas charge.
6 - Caution with Vacuum
and Refrigerant Fluid Charge
NeverNever
NeverNever
Never use the new compressor as a vacuum
pump. It may absorb dirt and water from the tubes,
which will be detrimental to its operation and
working life.
7 - Vacuum Pump
A - Always use a high vacuum pump;
B - Whenever possible, make a vacuum on the
high and low side;
C - Use a hose exclusively for each refrigerant:
one for R 134a and another for each of the
other refrigerants
D - Apply a vacuum until 500 μm Hg
(29.90" Hg), never less than 20 minutes
at this level;
E - It is recommendable to install a check valve at
the inlet of the vacuum pump.
8 - Refrigerant Fluid Charge
In domestic refrigeration systems as with most
work with little refrigerant fluid less than 350 g
(12.35 ounces) - and use a capillary tube as a control
element, the performance of the refrigeration system
will very much depend on the refrigerant fluid charge
used. Now, with alternative refrigerant fluids, it is even
more important to proceed correctly and use proper
equipment for this operation.
Example: a system with an internal volume of
280-300 liters normally operates with 90-120 grams
(3.2-4.2 ounces) of R 12 refrigerant.